PVI Industries Water Heater PV 413A User Manual

START-UP OF POWER VT® WATER HEATERS OR BOILERS  
**FOR DETAILED INFORMATION SEE INSTALLATION & MAINTENANCE MANUAL **  
WARNING: These startup instructions are prepared for a qualified service installer, service  
agency or gas supplier and require and rely on the experience and training of these  
qualified gas appliance technicians to be safely completed. Attempting to follow these  
instructions without such training and experience can result in property damage, exposure  
to hazardous materials, personal injury or death.  
1. Check the water heater tank to make sure it is full of water. (Remove air through T&P valve)  
2. Remove enclosure panel cover on the water heater to expose control circuit. A wiring diagram, included in this  
packet, will show the controls used in our circuitry.  
3. Visually check that all components are intact and no damage has occurred during transit.  
4. Check all connections within the control cabinet. A loose connection could cause intermittent shutdowns.  
5. Check flue gases with an electronic flue analyzer to make final settings of gas pressure regulator.  
6. The readings need to be taken from a hole in the vent several inches downstream of the fan outlet connection.  
7. Insert 0-6" W.C. manometer into the test opening in the vent. Pressure in stack should not exceed 2" W.C.  
8. When water in tank is above 120°F, insert analyzer or O2 testing in test opening; take O2 reading in percentage.  
9. Increase manifold gas pressure at the main gas pressure regulator taking O2 reading at each adjustment of gas  
regulator until optimum O2% (5-7%) is reached. If O2% decreases, reduce the gas pressure to last reading  
where the greatest reading is achieved.  
10. CO should not exceed 200 ppm. A reading greater than 200 ppm indicates lack of air. Reduce manifold gas  
pressure slightly and take readings until CO is within proper range. Optimum reading is no CO.  
11. If manifold pressure was changed during startup, take a final CO and O2 reading.  
12. Record CO2 and NOx if applicable. (See I&M if NOx measurement is required).  
13. Insert vent temperature gauge in test opening and read gross vent temperature; maximum gross stack is to be  
250°F. If an excessively high gross vent temperature is recorded, consult the factory.  
14. Check each operating and limit control to be sure they function properly by lowering and raising the temperature  
setting on each of the controls, causing burner to cycle on and off.  
15. NOTE: During the initial firing of the burner, smoke that is not related to the burner will be emitted from the  
heater. This is normal during "burn in" and could possibly continue for several hours.  
16. Complete the attached startup report.  
Important – Contact PVI Customer Service, 800-433-5654, if any recommended setpoint or analysis  
reading falls outside of the recommended ranges before completing startup.  
PV 413A 8/05  
 
Model Number:  
Serial Number:  
VENTING and COMBUSTION AIR  
Vent Material:  
Vent Diameter:  
(CPVC – Water Heaters Only; AL29-4C Stainless Steel – Boilers or Water Heaters)  
inches; Vent Length:  
Yes  
feet Vent Type:  
Through-the-roof  
Through Sidewall  
No  
Flue Damper  
Does vent have condensate drain?  
No  
Power Vent  
Yes; Qty:  
Yes; duct diameter  
Does vent have elbows?  
Yes; Qty  
Does vent contain any of these devices?  
Combustion air louvers or openings?  
Have direct-ducted combustion air?  
Duct Material:  
Draft Inducer  
Size:  
Draft Regulator  
Interlocked?  
No  
inches, length  
Yes  
No  
No  
feet.  
No  
Does duct have elbows?  
Yes; Qty  
GAS SUPPLY  
Type of Gas:  
Gas Supply Pipe Size:  
Combination Gas Pressure Switch Setting: High  
Natural  
LP  
Inlet Static Gas Pressure:  
“W.C. (14”W.C. maximum)  
“W.C. (see data label)  
Inlet Flow Gas Pressure:  
“W.C. Low  
“W.C.  
COMBUSTION ANALYSIS  
Boilers  
2nd Stage  
Heaters  
1st Stage  
Pilot Gas Pressure  
Manifold Gas Pressure  
Carbon Dioxide CO2 (8-9%)  
Oxygen O2 (5-7%)  
Carbon Monoxide CO (less than 200 ppm)  
Nitrogen Oxide NOX (if available)  
Vent Pressure (+.25” to + 2.0” W.C.)  
Gross Vent Temperature (maximum 230°F)  
less Room Temperature °F  
= Net Vent Temperature °F  
Important: You must submit the original copy of the completed form to your PVI representative before the  
warranty will become effective on this product. Contact Customer Service for assistance at 1-800-433-5654.  
Service Company Name:  
Service Co. Address:  
Start-up Performed By:  
Customer:  
Phone:  
Date:  
Phone No.:  
Date:  
Page 2 of 2  
PV 413 8/05  
817-335-9531 800-433-5654 FAX 800-880-2019 www.pvi.com  
 

Pelco Home Security System SYSTEM 9770 User Manual
Philips Indoor Furnishings 43199 87 16 User Manual
Philips MP3 Player AQ6508 User Manual
Philips Portable DVD Player PET703 User Manual
Philips Power Supply LR20PB6C User Manual
Philips TV VCR Combo CCZ254AT User Manual
Philips Universal Remote 6400 User Manual
Polaris Offroad Vehicle Sportsman 800 EFI User Manual
Poulan Lawn Mower 188695 User Manual
Printek Network Card Mt3 II Series User Manual